- for sectionalizing switch – overcurrent protection of an input cabinet.
Valve arc protection should have an alarm of valve operating. If a valve has misoperation, then (after 1 sec.) operating of a valve should be turned to switching off the circuit breaker.
ANNEXES
Annex А
(obligatory)
Supposed composition of microprocessor-based relay protection devices mounted at the substations 220 and 35 kV Lafarge
Table А.1
№ |
Name of the protected element |
Using function of protection or automatics |
ANSI code |
Manufacturer of protection or automatics device (cabinet) and its type |
||||
ABB |
Areva |
General Electric |
Siemens |
NPP «EKRA» |
||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
1 |
Transformer 220/35/6,6 kV 63 MV∙A Т1,Т2 |
Differential protection with deceleration |
87Т |
RET670RU2* |
Р633*** |
Т60* |
7UT633** |
ШЭ2607 041* |
Differential zero-sequence current protection |
87N |
- |
||||||
Gas protection of the transformer and OLTC |
63 |
ШЭ2607 041* |
||||||
OLTC contactor protection |
– |
|||||||
Overload current protection on the MV (LV) sides of the transformer |
50 (50 1ph) |
|||||||
Overcurrent protection on the HV side of the transformer |
51 |
Р143*** |
F650* |
7SJ64x** |
||||
Overcurrent protection on the MV (LV) sides of the transformer |
50,51 |
Р143*** |
F650* |
7UT633** |
ШЭ2607 043* |
|||
Earth-faults alarm on the MV (LV) sides of the transformer |
59N |
|||||||
Functional control of the voltage transformers on the MV (LV) sides of the transformer |
27 (59) |
|||||||
Voltage control |
27 (59) |
|||||||
Current control on the HV side of the transformer |
50,51 |
Table А.1 continuation
№ |
Name of the protected element |
Using function of protection or automatics |
ANSI code |
Manufacturer of protection or automatics device (cabinet) and its type |
||||
ABB |
Areva |
General Electric |
Siemens |
NPP «EKRA» |
||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
Automatic regulation of transformation ratio |
90 |
REU615RU *** |
KVGC202 *** |
ШЭ2607 157* |
||||
Breaking failure protection 220 kV |
50BF |
REC670RU* |
Р143*** |
C60* |
6MD66** |
ШЭ2607 019* |
||
Number of devices per one transformer |
RET670RU2 = 1 REU615RU = 1 REC670RU = 1 |
Р633 = 1 Р143 = 3 KVGC202 = 1 |
Т60 = 1 F650 = 2 C60 = 1 |
7UT633 = 1 7SJ64x = 1 6MD66 = 1 |
ШЭ2607 041 = 1 ШЭ2607 043 = 2 ШЭ2607 157 = 1 ШЭ2607 019 = 1 |
|||
2 |
Switchgear 35 kV |
Overcurrent protection |
50 |
SPAC8xx**** |
Р143*** (P141)*** |
F35* |
7SJ64x** |
БЭ2502* |
Zero-sequence current protection |
51N |
|||||||
Overload protection |
50/51 |
|||||||
Breaking failure protection |
50BF |
|||||||
Number of devices per feeder 35 kV |
SPAC8xx = 1 |
Р143(P141) = 1 |
F35 = 1 |
7SJ64x = 1 |
БЭ2502 = 1 |
|||
* The devices are approved by the conclusion of certifying commission for use at facilities of ОАО « UES FGC ». ** The devices are approved for participation in tender procedures conducted for the needs of OAO "UES FGC» (ОАО «UES FGC » letter № ЛМ-2550 from 17/07/09). *** Devices, which, at the time of the project developing, are on certification process at OAO "UES FGC". **** Devices, which, at the time of the project developing, are in the process of certification renewal. |